    Lumberg 隆堡0910 ASL 501 4點(diǎn)數(shù)量量輸入模塊
     WX20231102-140530@2x.png      

    Actuator Sensor-Interface (AS-Interface)

    AS-Interface was designed as a simple system for the quick data exchange of binary signals.  An international standard since 1999, in  accordance with EN 50295 and IEC 62026-2.

    Quick and Uncomplicated

    The biggest advantage of AS-Interface is the quick and uncomplicated installation of the  system. Communication (Manchester Encoding) and power are transmitted via a 2-wire cable. By using piercing technology for contacting to the cable it is possible to insert a new slave  at any point in the system. In addition, the arbitrary structure of the bus (line, tree,  star, ...) permits the perfect adaptation to the plant or machine. AS-Interface is mainly used for small machines, as a subsystem for more complex bus systems (e.g. PROFIBUS-DP) or as an easy introduction to bus technology.

    General Technical Data

    Transmission medium

    • Unshielded 2-wire cable for power supply (module electronics and sensors) and data transmission (Manchester Encoding)

    • Optional mechanically encoded flat or round cable

    Network topology

    The bus can be built arbitrarily (line, star, tree, ...). Terminating resistors are not required.

    Number of devices

    • 31 slaves by using standard slaves

    • 62 slaves by using A/B slaves with profile 3.0

    Reliable transmission rates and segment lengths

    • Transmission rate: 167 kBaud

    • Max. segment length: 100 m

    Addressing

    AS-Interface slaves are generally addressed via software (the default address is generally “0” for all AS-Interface slaves).

    This can be done in several ways:

    • Via the master: The slaves are connected to the master consecutively. The latter automatically identifies the kind of slave and builds up a communication. Then the slave can be addressed.

    • Via an addressing unit: All AS-Interface slaves can be addressed with the standard addressing unit “0913 ATL 003”.

    • Automatic addressing: If a slave in a network fails, AS-Interface offers the chance of auto-addressing. The defective slave is replaced by an identical one. The master identifies this slave and automatically addresses it to the address of the missing slave