    西門子S7-1200模塊 電能測量模塊 6ES7238-5XA32-0XB0

    點擊圖片查看原圖
    品牌: 西門子
    重量,約: 165 g
    單價: 面議
    所在地: 北京
    有效期至: 長期有效
    最后更新: 2021-07-12 16:18
    瀏覽次數(shù): 219
    詢價
    店鋪基本資料信息
     
    產(chǎn)品詳細說明
    西門   PLC  模塊  電能測量模塊 6ES7238-5XA32-0XB0

     
    SM 1238 電能測量模塊 480V AC

     技術(shù)數(shù)據(jù)

    Technical data

    SIMATIC S7-1200, Analog input, SM 1238 Energy Meter 480 V AC, power measurement module for data acquisition in 1- and 3-phase supply systems (TN, TT) up to 480 V AC; Current range: 1 A, ***; acquisition of voltage, current, phase angles, power, energy values, frequencies; Channel diagnostics
    General information
    Product type designation SM 1238, AI energy meter 480 V AC
    HW functional status From FS02
    Firmware version V2.0.1
    Product function
    ● Voltage measurement Yes
    — with voltage transformer Yes
    ● Current measurement Yes
    — without current transformer No
    — with current transformer Yes
    ● Energy measurement Yes
    ● Frequency measurement Yes
    ● Power measurement Yes
    ● Active power measurement Yes
    ● Reactive power measurement Yes
    ● I&M data Yes; I&M 0
    ● Isochronous mode No
    Engineering with
    ● STEP 7 TIA Portal configurable/integrated from version V13 SP1
    Operating mode
    ● cyclic measurement Yes
    ● acyclic measurement Yes
    ● Acyclic measured value access Yes
    ● Fixed measured value sets Yes
    ● Freely definable measured value sets No
    CiR - Configuration in RUN
    Reparameterization possible in RUN Yes
    Calibration possible in RUN Yes
    Installation type/mounting
    Mounting position Horizontal, vertical
    Supply voltage
    Design of the power supply from CPU
    Type of supply voltage DC
    Input current
    Current consumption, max. 180 mA
    Power loss
    Power loss, typ. 0.75 W
    Address area
    Address space per module
    ● Address space per module, max. 124 byte; 112 byte input / 12 byte output
    Time of day
    Operating hours counter
    ● present Yes
    Analog inputs
    Cycle time (all channels), typ. 50 ms; Time for consistent updat of all measured and calculated values (cyclic und acyclic data)
    Interrupts/diagnostics/status information
    Alarms
    ● Diagnostic alarm Yes
    ● Limit value alarm Yes
    ● Hardware interrupt No
    Diagnostics indication LED
    ● Monitoring of the supply voltage (PWR-LED) Yes
    ● Channel status display Yes; green LED
    ● for channel diagnostics Yes; red Fn LED
    ● for module diagnostics Yes; green/red DIAG LED
    Integrated Functions
    Measuring functions
    ● Measuring procedure for voltage measurement TRMS
    ● Measuring procedure for current measurement TRMS
    ● Type of measured value acquisition seamless
    ● Curve shape of voltage Sinusoidal or distorted
    ● Buffering of measured variables Yes
    ● Parameter length 74 byte
    ● Bandwidth of measured value acquisition 2 kHz; Harmonics: 39 / 50 Hz, 32 / 60 Hz
    Measuring range
    — Frequency measurement, min. 45 Hz
    — Frequency measurement, max. 65 Hz
    Measuring inputs for voltage
    — Measurable line voltage between phase and neutral conductor 277 V
    — Measurable line voltage between the line conductors 480 V
    — Measurable line voltage between phase and neutral conductor, min. 0 V
    — Measurable line voltage between phase and neutral conductor, max. 293 V
    — Measurable line voltage between the line conductors, min. 0 V
    — Measurable line voltage between the line conductors, max. 508 V
    — Internal resistance line conductor and neutral conductor 3.4 M
    — Power consumption per phase 20 mW
    — Impulse voltage resistance 1,2/50µs 1 kV
    — Measurement category for voltage measurement in accordance with IEC 61010-2-030 CAT II; CAT III in case of guaranteed protection level of 1.5 kV
    Measuring inputs for current
    — measurable relative current (AC), min. 1 %; Relative to the secondary rated current 5 A
    — measurable relative current (AC), max. 100 %; Relative to the secondary rated current 5 A
    — Continuous current with AC, maximum permissible 5 A
    — Apparent power consumption per phase for measuring range 5 A 0.6 V·A
    — Rated value short-time withstand current restricted to 1 s 100 A
    — Input resistance measuring range 0 to 5 A 25 m At the terminal
    — Surge strength 10 A; for 1 minute
    — Zero point suppression Parameterizable: 2 ... 250 mA, default 50 mA
    Accuracy class according to IEC 61557-12
    — Measured variable voltage 0,2
    — Measured variable current 0,2
    — Measured variable apparent power 0.5
    — Measured variable active power 0.5
    — Measured variable reactive power 1
    — Measured variable power factor 0.5
    — Measured variable active energy 0.5
    — Measured variable reactive energy 1
    — Measured variable neutral current 0.5; calculated
    — Measured variable phase angle ±1 °; not covered by IEC 61557-12
    — Measured variable frequency 0.05
    Potential separation
    Potential separation channels
    ● between the channels and backplane bus Yes; 3 700V AC (type test) CAT III
    Isolation
    Isolation tested with 2 300V AC for 1 min. (type test)
    Standards, approvals, certificates
    CE mark Yes
    CSA approval Yes
    UL approval Yes
    cULus Yes
    FM approval Yes
    RCM (formerly C-TICK) Yes
    KC approval Yes
    Marine approval Yes
    Ambient conditions
    Ambient temperature during operation
    ● horizontal installation, min. -20 °C
    ● horizontal installation, max. 60 °C
    ● vertical installation, min. -20 °C
    ● vertical installation, max. 50 °C
    Dimensions
    Width 45 mm
    Height 100 mm
    Depth 75 mm
    Weights
    Weight, approx. 165 g
    Other
    Data for selecting a current transformer
    ● Burden power current transformer x/1A, min. As a function of cable length and cross section, see device manual
    ● Burden power current transformer x/***, min. As a function of cable length and cross section, see device manual